Page 1
Characteristics of
O2
·
O2
is an odorless, tasteless and colorless gas that supports
life. While it is not flammable, it does support fire
·
The normal FiO2
of the atmosphere is 20.9%
·
While the FiO2
stays the same, the weight of the atmosphere
decreases as one moves away from sea level so that the PO2
drops.
·
The atmosphere is 760 mmHg at sea level & only 226 mmHg at
30,000 feet
·
O2
is a paramagnetic gas that changes a magnetic field, this
fact is the basis for at least one kind of
O2
analyzer.
·
O2
is only slightly more dense than air but less dense than CO2
·
O2
is more viscous than air
The density and the viscosity of
various gases change their flows through flow meters.
Thus interchanging flow meters between different gases may
result in inaccurate readings.
The
O2 flowmeter is not accurate with Helium, nor with air.
The manufacturing of
O2.
·
States of matter
·
All substances have 3 states of matter: gas, liquid and solids
o
These states of matter are changed by temperature alterations
o
As the molecules move faster in higher temperatures, they start
to change from solid to liquid and if they get high enough the
fastest molecules move from liquid to a gas state. This
movement is called "boiling off."
EXAMPLE: ice [solid] melts into
water [liquid], which then can move into water vapor [gas].
·
Liquid O2
has a boiling point at –183
°C in which it turns
into a gas.
·
Other gases melt at different temperatures & boil off at
different temperatures
·
As a gas is compressed it becomes hotter because of the increase
in kinetic energy
·
When only a few molecules of a liquid move into the gas state
below the boiling point, this is known as evaporation
·
Just as water changes size as it moves through the different
states of matter, liquid
O2
expands 862 times as it moves into
the gas state.
·
More
O2
can be kept at the liquid state than at the gas state.
All you have to do is keep the
O2
cold enough [below -183
degrees]
Commercial manufacture of
O2:
Done via a process called FRACTIONAL DISTILLATION of liquid air.
There are other methods of making
O2 but this is the most
economical means.
·
Purification: an air compressor pulls in air through filters
from the atmosphere into the device where it is compressed to
1500 psig, then the resulting heat is dissipated before further
compression to 2000 psig. At each stage of compression and
expansion the temperature drops and more water leaves the air.
Finally the air is cooled by heat exchange [a refrigerator] to
-50
°C where the water vapor is frozen out of the gas.
Water and a lot of impurities are gone by now.
·
Liquefaction: air continues to be cooled down by several steps
of compression and expansion until it is liquid air which is
sent to a distillation tower.
·
Distillation: as the liquid air moves down the fractional
distillation tower, it warms slowly. At different levels,
different gases will boil off at their own boiling points. Each
gas is captured at this level and sent down a pipe as a pure
gas. At one level the purified
O2
gases are captured in this
manner. The pure
O2
is sent to storage cylinders or cooled off
into LOX again.
Compressed air [O2, nitrogen and trace gases]
·
There are several levels of compressed air [A through J] only J
is pure enough for medical uses
·
Some hospitals use air compressors to pull air in from the
environment and compress it to 60 psig for use in the hospital.
·
Respiratory care equipment is made to operate at 50-60 psig
·
Air compressors
o
Some are huge air compressors that power piping systems to the
ICU beds, surgery, Neonatal ICU and other selected areas
o
Other have smaller high pressure air compressors that are used
in the hospital and the home to power ventilators between 50-60
psig
o
A few ventilators have their own built-in air compressors
o
And still others can work off the hospitals piped in air but
have a automatic back up air compressor that kick in when the
gas pressure in the wall drops to a critical level
o
There are tiny air-compressors that use used to deliver SVN
medication. These rarely exceed 10 lpm & cannot operate
ventilators or flow meters.
o
The gas is only as clean as it's source
·
When there are filters/dryers in the air line, all ventilators
and other pieces of equipment that interface with the air line
need to have their own high pressure filters/dryers to protect
the internal structure of the machines from humidity and other
impurities in the air lines
Carbon dioxide gas & the specific characteristics of CO2
·
Carbon dioxide makes up a small portion of the atmosphere [only
.03%] it is a byproduct of both cellular respiration &
incomplete combustion.
·
If CO2
replaces
O2, it will not support life
·
CO2
is used to power carbonated drinks, in fire extinguishers
and as "dry ice" it is used to chill food
·
In the hospital, CO2
tanks are used to calibrate arterial blood
gas machines. For the ABG machine to accurately measure CO2
in
the blood, it must be exposed to both high and low level of CO2
for the two-point calibration needed for precise measurement of
blood PaCO2.
·
As PaCO2
levels rise in the bloodstream, the brain responds by
increasing both the breathing rate and Vt. The Ve changes will
change the PaCO2. Decreased PaCO2
triggers the brain to return
the Ve to baseline.
·
However once the CO2
gets excessively high, the patient becomes
confused, then loses consciousness
Percentages of medical CO2 used in
this country?
·
Various specific percentages are used for the different blood
gas machines. there are generally two tanks of CO2
mixtures, a
high and a low percentage.
·
When delivered to a patient one would mix it with
O2
at the
following percentages:
o
95% 02 / 5% CO2
o
90% 02 / 10% CO2
Why do we not want to use a humidifier when we deliver CO2?
Years ago, CO2 was given to increase blood flow to the brain in
cases of stroke and to treat hiccups. Because CO2 is dangerous,
this is not done anymore.
If a new use for CO2 is discovered,
you need to know that:
·
CO2
and water make carbonic acid, so humidified CO2
stings the
face.
·
Deliver it dry with a hand-held none-rebreathing mask
·
The RCP should not leave the patient
·
Constantly monitor respiratory rate, heart rate and blood
pressure
·
Stop, if patient losses consciousness
·
Give for no more than 10-15 minutes
·
Never give CO2
to a person with chronic hypercapnia
The use of helium as a medical gas:
·
Helium is a light gas. Its density is only 1/6th of air's
density
·
Because the gas density is so low, the presence of He in the
upper airways changes the sound of the vocal cords
·
The gas can move around upper airway obstructions
·
Administration of
O2
Helium mixtures [Heliox] is used to treat
hypoxemia in those persons whose problem is partial upper airway
occlusion
·
Helium is a rare gas; it is distilled from a natural gas that is
found only in Texas, in one place in Canada and by the Black
Sea. The USA government keeps a monopoly on He because of this.
·
Helium does not support life so it must be mixed with
O2
o
80% He /20%
O2
o
70% He/30%
O2
o
Administered with a non-rebreathing mask
Hazards :
·
Hypoxia. There have been a few occasions where commercial tanks
of Heliox separated. The He would rise to the top of the tanks
while the more dense
O2
would drop. The RCP might need to
analyze the
O2
before it gets to the patient.
·
Due to the density of helium, it is a poor transporter of
aerosolized medication
·
Because it is so low in density it impairs the cough
·
Heliox mixtures will not be accurately displayed by a
O2
flow
meter.
If one uses the 80/20 mixture, the
set flow rate must be multiplied by a factor of 1.8 to get the
true flow rate
If one uses the 70/30 mixture, the
set flow rate must be multiplied by a factor of 1.6 to get the
true flow rate
Bulk gas delivery system. What is the volume of a bulk gas
system?
·
Because the amount of
O2
used in even a small hospital is so
huge, the gas is generally piped into the building
·
Once a clinic's gas reserves reach 20,000 cubic feet, one is now
working with a bulk system
·
Operation of a bulk gas delivery system falls under the rules of
the Compressed Gas Association, [CGA], the national Fire
protection agency [NFPA] and other agencies dictating state and
local building codes
·
The Joint commission on Accreditation of Healthcare
Organizations [JCAHO] plays a big part in the regulation of
these systems
Terms:
·
Banks: multiple cylinders attached to each other in a line. Each
cylinder must have a check valve between it and the mainline
·
Check valves: a one-way valve that prevents gas from a single
leaky cylinder to deplete the entire system
·
Headers: connection between two high pressure lines
·
Main line: pipes that connect the operating supply to the risers
and the branches
·
Risers: pipes that rise between floors
·
Lateral branches: horizontal pipes that that move out from the
riser to the rooms or groups or rooms on each floor
·
Manual shut off valves: valves that can be shut off by hand by a
simple gesture
o
Manual shutoff valves will be used in case of a fire downstream
o
Manual shutoff valves will be used in cases of repairs
downstream
·
Zone valves: manual shutoff valves located in branch and riser
lines. One could isolate an entire area so that repairs could be
done without shutting down the entire system.
o
Quarter turn to shut off
o
The tech should be able to do this standing up
o
Zone valve for every riser and for every branch
o
Zone valve just upstream for every critical area or life support
area
o
Zone valve for every operating room
·
Pressure gauges: dial in which one can read the pressure in the
line at that point.
o
Each zone valve will have one
o
It should be easily read standing up
o
It should be labeled with the gas it measures
Three
types of central supply of medical gases
·
Located outside the building with a control panel protected from
the weather
·
Located in a building outside the main building
·
Located in a room in the building that is used for that purpose
·
Alternating supply system or cylinder supply without reserve
Two banks are attached to the main
line to the hospital. Each bank must hold 24 hours of
O2 for
that hospital
·
Each bank has:
o
More than two cylinders
o
Have a check valve before it gets to the main line
o
Have a pressure regulator
o
A shut off valve for emergencies
·
At the main line there is a change-over actuating switch that
will automatically switch between the two banks
o
The one being used is the primary bank and the other is the
backup
o
The changeover is stimulated by a drop in the banks' line
pressure
o
The tanks of the backup bank can now be changed
·
The alternating system without a reserve is used in small
clinics or with the anesthesia gases in larger hospitals
Cylinder supply with reserve supply
·
Primary & secondary systems are generally liquid
O2
with a bank
of three or more cylinders as a reserve system
·
Day to day operations go like this:
o
The gas deliver alternates between the primary and the secondary
systems with the reserve only being used for emergencies such as
failure of both the primary and secondary gas systems or for use
during repairs to one of these systems
o
Each primary system has check valves between it and the
secondary system and each has pressure relief devices as well as
pressure gauges
o
Reserve tanks have check valves and shut-off valves and a
pressure gauge
o
Some systems have pressure gauges in series as failsafe systems
·
Bulk systems with reserve: liquid
O2
with reserve as smaller
liquid or as gas in cylinders
o
The reserve must be located outside the primary supply location
or building
o
Manually controlled shut off valves are needed
·
Upstream of all pressure regulators
·
Pressure pop off valves are set to relieve pressure when it
reaches more than 50% of normal
Hospital air compressors
·
The hospital should have two air compressors of equal size and
each one should be able to deliver 100% of the required air
needs.
·
Each compressor should have its own pressure relief valve, check
valves and isolation valves
·
Compressed air is pressured to working pressure then sent to a
cooling area where the water vapor is removed and later to a
dryer for further removal.
·
Medical gas should be clean but not sterile because it is not a
drug [per the FDA]
Why is
O2
stored so often in liquid form?
·
We can hold 860 times more liquid
O2
than gas
·
There is less exchange of banks
·
These are usually refilled from delivery trucks with indexed
connectors
·
NFPA regulates the site of liquid
O2.
How does the liquid
O2
stay liquid?
·
It is kept cooled to below its boiling point. At –300
°F.
·
The stainless steel storage tanks are like huge thermos bottles
with double walled insulated walls. There is a vacuum layer for
added insulation.
·
As it is needed in the piping system, the liquid
O2
flows into
coils where it is warmed up by exposure to the elements and the
O2
inside the coils gets warmer and liquefies
·
These coils stay iced over, even in the dead of summer
Discuss the piping systems of
O2
and compressed air.
·
Seamless copper or brass pipes
·
Different gases have different diameters of pipes
How often are the pipes labeled?
Pipes should be labeled with the gas
at least every 20 feet and/ or as it goes through a wall into a
room. One should never look up at a pipe without being able to
see what gas it contains
Discuss area alarm systems:
·
Audible & visual arms are required in every vital area
·
These must deliver a loud and non-cancelable visual alarm if the
operating pressure drops 20%
·
When the alarm goes off there should be a policy for calling the
appropriate maintenance persons who maintain the line.
What are station outlets?
·
The station outlet is the final unit of the supply system. This
outlet is where the RCP attaches the flow meter or the high
pressure hoses for the ventilators
·
The working pressure at the station outlet for air would be 60
psig and the working pressure for
O2
is 50 psig.
·
The station outlet will be at the patient bedside
·
The station outlet could have [1]
O2
outlet [2] compressed air
out let [3] vacuum outlet
·
The base block which is equivalent to the face plate of an
electrical plug will have clear labels for the gas they contain
·
Each outlet will have a check valve that only opens up to the
flow when there is a high-pressure hose or a flow meter attached
to it.
o
If the male and female parts are not connected there will be no
flow
o
Remember that once these check valves are opened gas can go both
ways. A leaky RC device could leak
O2
out of the wall or leave
the appliance to enter the wall depending on the pressures of
the wall and the appliance.
o
If the appliance leaks, the device may need to be disconnected
or the flow meter turned off so that the gas will not be wasted.
Means to avoid accidental connection of the wrong parts: the
appliance or the flow meters will be attached to the station
outlet with gas specific connectors
·
DISS: diameter index safety system: different diameters of the
threaded connections interface hoses or devices under 200 psig.
o
There are 2 specifically sized bore that must fit the shoulders
for the connection to make
o O2
has a #1240 CGA connection
·
Quick connects: NCG and Ohio. These connections are faster,
because they just plug in with a single motion. These are also
connections for hoses and devices under 200 psig
o
While quicker, these are prone to leaks
Use of gas cylinders to deliver gas to patients
·
Gas cylinders or tanks are used to store high-pressure gas or
gas mixtures at max pressures of 2000 psig.
·
These are used to supply O2 during transport or to remote areas
of the hospital
Page 2
Construction of the gas cylinder
·
Medical gas cylinders are constructed of steel, aluminum or
chrome-molybdenum
o
Aluminum tanks are used for transport particularly air transport
o
For home use
o
For transferring a patient to a MRI area where magnetized metals
are dangerous and forbidden
·
Cylinders are made by shaping a tube which is seamless
·
The neck is narrowed then threaded to fit a valve stem
·
The bottom should be flat enough so that the tank can stand on
the floor without support
·
Some tanks are spun around a mold then sealed with very high
heat
How do we test tanks?
·
Cylinders are inspected every 5-10 years
·
The inspector looks for rust, dents and corrosion
·
The inspector will lightly tap the side of the cylinder with a
hammer to listen for the clear tone created by the hammer. This
should last 2-3 seconds
·
The valve stem is removed and the inside is examined with a
light for rust.
What is hydrostatic testing?
·
The tank is immersed in a water bath while empty.
·
Then the tank is filled to 3000 psig [remember it is supposed to
hold 2000 psig
·
As the gas enters the cylinder, the excessive pressure will
cause weakened tank walls to swell and water will be displaced.
How do we know when the last time a tank was inspected?
·
The inspector will stamp the tank on the shoulder with his
personal mark as well as the month and year of the inspection
·
He will indicate the next testing [5 or 10 years]
·
He will display the test results [elastic expansion]
What are all the marks on the shoulder of the gas cylinder?
·
Front of the tank
o
DOT: department of transportation
o
3AA material used in construction
o
2015 filling pressure in psig
o
Size and serial number of the tank
o
Owner of the tank
o
Mark of the inspector
·
Rear of the tank
o
Mode of construction
o
Date of inspection
o
Star means that the tank can be inspected every 10 years
o
EE is the elastic expansion during testing
What is found on the paper label of the gas cylinder?
·
The contents of the tank- the exact gas composition found on the
left
·
Color coded hazard class inside a diamond
o
Non-flammable [green]
o
Flammable [red]
o
Oxidizer [yellow]
·
Signal words: displayed to denote the seriousness of the gas
·
If the gas is poisonous, a second diamond is displayed
·
List of detailed cautions regarding the contents
·
The name and address of the manufacturer
What is found on the hanging tab
·
Identification of contents
·
Perforated tag labeled FULL, IN USE, EMPTY
o
Pull off the FULL portion once the tank is opened,
o
Once the tank is used up, pull off the IN USE to leave only the
EMPTY sign
o
Then empties are placed together and returned to the
manufacturer for refill
Agencies that regulate the markings and labeling of cylinders
·
FDA & DHHS regulates the purity of the gas
·
DOT regulates the handling and the shipping of tanks
What are the colors of the cylinders holding the gases used in
respiratory care?
|
Oxygen 02 |
Compressed air |
helium |
nitrogen |
Carbon dioxide/02 mixture |
Heliox
He/02 mixture |
|
Green USA
White international |
yellow |
brown |
black |
gray shoulder with green body |
brown shoulder with green body |
|
IMPORTANT NOTE: Color coding is
only a guide.
You should always read the label and if in doubt,
don't administer the gas. |
Compare the E cylinder to the H cylinder.
·
While there are many sizes of medical gas tanks, the two most
commonly used in the hospital setting are the E and H cylinders
for
O2.
·
Size
o
The E cylinder is the smaller one
o
The H cylinder is the larger one [10x bigger]
·
The valve stem
o
the tops of all cylinders narrow at the shoulders into the neck
o
the valve stem sits in the neck and when twisted it opens the
cylinder for the gas to escape the tank
·
The E cylinder’s valve stem is opened and closed with a wretch
[commonly called a
O2
Key or Key] & this opening is flush to the
valve stem
·
The E cylinder’s valve stem fits into a YOKE type of connector
to the gas regulator which will control the pressure and the
flow of the gas as it leaves the tank
·
The E cylinder outlet must include an O ring or washer for the
regulator to fit without leaking gas
·
The H cylinder’s valve stem is opened by turning the wheel
handle welded onto the valve stem
·
The H cylinder contains a male connector onto which a
regulator's threaded inlet will fit
There are two basic types of valve
stems
·
Packed: direct valve stem uses resilient packing to prevent
leaks, these take higher pressures & are cheaper than the
diaphragm. It takes two or three turns to open
·
Diaphragm: indirect valve which raises the stem, raises the
diaphragm. It opens with only a quarter turn or a ¾ turn
Valve outlets: both E and H
cylinders have coverings over the outlets.
·
Brand new E cylinders have a white plastic covering
·
H cylinders have an aluminum cover
Pressure relief devices: to prevent
rupture of the entire cylinder in the case of increased
pressures [increased temperatures or over filling] gas tanks
contain various types of pressure relief devices
·
Disc ruptures at high pressure to vent gas
·
Spring-loaded pressure valves are usually in the larger tanks
·
Fusible plug which melts at the high temperatures associated
with excessive pressure
How is the H cylinder opened?
The valve stem on the H tank is
opened by turning the hand wheel counter clockwise [turn to the
left to loosen]
Compare the index safety systems for both types of tanks